MF Booster Set are hydro-pneumatic operation (i.e. pressure switch operated). With a maximum recommended four pumps & jockey pump.
Any combination of pump operation is available:-
DS (duty/standby) 100% each pump
DA (duty/assist) 50% each pump
DAA (duty/assist/assist) 33.3% each pump
DAS (duty/assist/standby) 50% each pump
DAAA (duty/assist/assist/assist) 25% each
DAAS (duty/assist/assist/standby) 33.3% each
With a jockey pump normally selected to provide 10% of duty for larger flows usually above 10 l/s.
Pumps are either end-suction, horizontal multistage or vertical multistage - application and duty dependant.
The accumulator is full sized to provide maximum storage and reduce pump starts on small demands.
Pipework is stainless steel.
Standard control panel is IP65 & switched as volt free contacts for all alarm states & low level protection contacts.
Sets available with optional WRAS approved break tank sized to suit demand. Break tanks mounted over up to 3000 litres nominal capacity & alongside up to 9000 litres capacity.
Recommended extras include:-
WRAS listed pressure reducing valves
WRAS approved potable water standard flexibles
WRAS listed low water float switches
Twin pump variable speed, variable flow, constant pressure inverter-driven booster set giving the option of either duty/standby 100% each pump or duty/assist 50% each pump.
Designed for the domestic/light commercial applications i.e. schools, colleges, office blocks, nursing homes etc.
TKS sets are compact in design and quiet running.
230/1/50 supply required.
Available as economy version (no panel) or as full FP version c/w IP55 control panel.
Sets available with optional WRAS approved break tank sized to suit demand. Break tanks mounted over up to 3000 litres nominal capacity & alongside up to 9000 litres capacity.
Recommended extras include:-
WRAS approved potable water standard flexibles
WRAS listed low water float switches
Designed for reduced capital costs fitted with 2 stainless steel pumps giving either duty/standby 100% each pump or duty/assist 50% each pump operation
E-HM2-4(1) – E-C12033(1) model available with 230/1/50 supply & 2 No 400/3/50 model E-C7045(3) & E-C12033(3)
Flow/Pressure range 0.5 l/s – 5 l/s @ 1 - 5 Bar
These sets are hydro-pneumatic i.e. pressure switch operated
Sets are complete with stainless steel pipe-work incorporating isolation valves for the pumps & manifolds as well as non-return valves.
Handing option as standard with manifold connections available at either end.
Recommended extras include:-
WRAS listed pressure reducing valves
Potable water standard flexibles
WRAS listed low water float switches
Designed to supply cold water to bib taps, hose reels irrigation and any application with a start/stop demand.
Typically supplied with 230/1/50 stainless steel horizontal multistage pumps from 0.55 kW - 1.1 kW
The fluid controller starts the pump on demand & continues to run until the demand stops. The controller also incorporates low water protection & three indicator lamps:-
Green: mains power
Yellow: pump run
Red: fault lamps
NB. These units are not suitable for applications that have cistern valves i.e. WC's or where expansion vessels are fitted.
Designed specifically for Cat 5 backflow protection applications. This booster incorporates a 54 litre break tank c/w water regulation category 5 protection.
Applications:-
Hygienic Rooms
Laboratories
Veterinary Surgeries
Garden irrigation
Bib taps
Bin Stores
Abattoirs
Mortuaries
Multi-storey window wash
Multistage stainless steel 230/1/50 pumps from 0.55 kW - 1.1 kW
Green: mains power
Yellow: pump run
Red: fault lamps
NB. These units are not suitable for applications that have cistern valves i.e. WC's or where expansion vessels are fitted.