Products
Services
Operations & Maintenance Instructions
Client Projects
Offers section
About the Company
Downloads
Contact Us
Sitemap
 
Pressurisation

Micro-S Digital Pressurisation Unit

Main features include

  • 2-digit digital display
  • Quick indication of High Pressure (HP) and Low Pressure (LP) faults
  • Compact wall-hung design
  • Possibly the smallest full sized peripheral pump operated pressurisation unit in the UK
  • Non-dependant on mains pressure to satisfy system pressure requirements
  • Option of second float valve where water mains pressure is low
  • All mechanical connections exit the base. Electrical connections on either side.
  • Strong 1.5mm mild steel construction fully powder coated
  • Pump anti seize pulse feature
  • Economically priced

 


Micro-S Pressurisation Unit




Internal view showing the full sized pump

Main features include:-

  • Compact wall-hung design
  • Possibly the smallest full sized peripheral pump operated pressurisation unit in the UK
  • Non-dependant on mains pressure to satisfy system pressure requirements
  • Option of second float valve where water mains pressure is low
  • All mechanical connections exit the base. Electrical connections on either side.
  • Strong 1.5mm mild steel construction fully powder coated
  • Pump anti seize pulse feature
  • Economically priced

Download (pdf):
Micro-S Pressurisation Unit

 


EPS - Pressurisation Unit

Electronic single pump pressurisation unit for use on heating & chilled water systems with a cold fill pressure up to 2.8 Bar.  Can be either floor or wall mounted.

Main features include:-

  • System pressure LED indication
  • High pressure LED indication
  • Low pressure LED indication
  • Transducer failure LED indication
  • Service indication
  • Pump fuse/fail LED indication
  • Low water LED indication
  • Anti seize pulse turns the pump over every 12 hrs
  • The unit has a system fill mode for initial filling of the system
  • Pump test button

EPS-HP version:  As above but fill pressure of 6.0 Bar

Download (pdf):
EPS - Pressurisation Unit

 


EPT - Pressurisation Unit

Electronic twin pump, duty/standby pressurisation unit for use on heating & chilled water systems with a cold fill pressure up to 2.8 Bar.  Can be either floor or wall mounted.

Main features include:-

  • System pressure LED indication
  • High pressure LED indication
  • Low pressure LED indication
  • Transducer failure LED indication
  • Service indication
  • Pump fuse/fail LED indication for P1 or P2
  • Pump 1 test button
  • Pump 2 test button
  • Pump rotation
  • Low water LED indication
  • Anti seize pulse turns the pump over every 12 hrs
  • The unit has a system fill mode for initial filling of the system.

EPT-HP version:  As above but fill pressure of 6.0 Bar

Download (pdf):
EPT - Pressurisation Unit

 


EPS-ENH - Enhanced Pressurisation Unit

Electronic single pump pressurisation unit for use on heating & chilled water systems with a cold fill pressure up to 2.8 Bar.  Can be either floor or wall mounted.

Main features include:-

  • System pressure LED indication
  • High pressure LED indication
  • Low pressure LED indication
  • Transducer failure LED indication
  • Service indication
  • Pump fuse/fail LED indication
  • Low water LED indication
  • Anti seize pulse turns the pump over every 12 hrs
  • The unit has a system fill mode for initial filling of the system
  • Pump test button

Main enhanced features:-

  • 20 character 2 line LCD display
  • Door interlocked Isolator
  • The digital display indicates all conditions with additional lamps for:-
    • Alarm activated
    • Low water
    • Pump auto operation
    • Pump hand
    • Pump off
    • Pump run
    • Pump trip
  • Remote Start/Stop
  • Volt free contacts for:-
    • Pump run
    • Pump trip
    • Low water level
    • High water level
    • Low pressure
    • High pressure
    • Frequency starts
    • Flood alarm
    • Transducer failure

EPS-ENH-HP version:  As above but fill pressure of 6.0 Bar

Download (pdf):
EPS-ENH-Pressurisation Unit

 


EPT-ENH - Enhanced Pressurisation Unit

Electronic twin pump, duty/standby pressurisation unit for use on heating & chilled water systems with a cold fill pressure up to 2.8 Bar.  Can be either floor or wall mounted.

Main features include:-

  • System pressure LED indication
  • High pressure LED indication
  • Low pressure LED indication
  • Transducer failure LED indication
  • Service indication
  • Pump fuse/fail LED indication
  • Low water LED indication
  • Anti seize pulse turns the pump over every 12 hrs
  • The unit has a system fill mode for initial filling of the system
  • Pump test button

Main enhanced features:-

  • 20 character 2 line LCD display
  • Door interlocked Isolator
  • The digital display indicates all conditions with additional lamps for:-
    • Alarm activated
    • Low water
    • Pump 1 auto operation
    • Pump 2 auto operation
    • Pump 1 hand
    • Pump 2 hand
    • Pump 1 off
    • Pump 2 off
    • Pump 1 run
    • Pump 2 run
    • Pump 1 trip
    • Pump 2 trip
  • Alternating pump start
  • Remote Start/Stop
  • Volt free contacts for:-
    • Pump run for both P1 & P2
    • Pump trip for both P1 & P2
    • Low water level
    • High water level
    • Low pressure
    • High pressure
    • Frequency starts
    • Flood alarm
    • Transducer failure

EPT-ENH-HP version:  As above but fill pressure of 6.0 Bar

 


MS1 / MS1 ENHANCED

SUPERSEDED BY ELECTRONIC RANGE 2009

 


MT1 / MT1 ENHANCED


SUPERSEDED BY ELECTRONIC RANGE 2009

 


MS2 / MS2 ENHANCED

SUPERSEDED BY ELECTRONIC RANGE 2009

 


MT2 / MT2 ENHANCED

SUPERSEDED BY ELECTRONIC RANGE 2009

 


WS1 / ES1 / OS1



SUPERSEDED BY ELECTRONIC RANGE 2009

 


Expansion Vessels

A full range of fixed air charge vessels is carried in stock from 3 litre to 1000 litre.
Standard range are 10 bar rated and with a 99oC max temp rating.
Steel shell with either Butyl or EPDM rubber diaphragms c/w stainless steel connection.
For use as heating & chilled water sealed systems or as secondary hot water expansion vessels for mains feed or boosted hot water generation.
Available from 3-12 litre as pipeline standard mounted. Available from 24 – 300 litre as horizontal or wall mounted versions. Available from 50 – 1000 litre as vertical floor mounted versions.
N.B. Expansion vessels should always be installed with a Lock Shield isolating valve & drain to allow the vessel to be fully drained before setting the air charge.
We recommend annual servicing/refitting the vessel air charge

Download (pdf): Expansion Vessels